ecobee aux heat not working

Why is my ecobee rebooting? ecobee recommends turning off the compressor when outdoor temperatures drop below 35˚F; however, this setting is not ideal for energy efficiency and costs. This site also participates in other affiliate programs and is compensated for referring traffic and business to these companies. For the past two years, whenever the outdoor temp has dropped below 40 degrees or so, the aux heat is supposed to kick in. I reinstalled the old thermostat and it is working as expected (heat + fan). Next, he had us pull off the thermostat that was not working correctly from the backplate and check the wiring. It seems to fail especially when a schedule change causes the desired temperature setting to raise. Ecobee gives users a lot of control over their thermostat. If your heat still isn’t turning heat, call Ecobee customer service for additional support: 877-932-6233. My ecobee thermostat won't turn on. Other reasons that the heat may not be turning on are specific thermostat settings or a furnace problem. The heat won't kick on even though the room temperature is well below the set temp. tgrant48 November 14, 2019, 3:50pm #2. Maintenance Reminder: You are due for regular maintenance. The furnace is overheating. Maintenance Reminder: HVAC system due for regular maintenance. You will see the set point temperature displayed in a box under the current temperature. Sale. Hey guys, I think I'm having a problem whereby the Ecobee isn't actually activating the auxiliary heat on my heat pump. When it gets below 35 degrees, a heat pump loses its efficiency and cannot keep up with the heat loss of the structure. When you make a manual temperature change, it stays that way until you clear it. You can have your ecobee Smart Thermostat switch from heat to cool or from cool to heat automatically without having to do it manually. Check out this article for more information about the Power Extender Kit and how to install it. The target temperature is the temperature that the device attempts to achieve. When temperatures get very cold here (say, 20 or below), my condo really struggles to maintain temperature, while giving me alerts that the Aux has been running too long. 4) Auxiliary heat is malfunctioning Below 40 degrees, your heat pump struggles to heat your home. My Ecobee alerted me this morning (on the Thermo Screen) that AUX had been running too long. Follow these steps to change the fan control: Main Menu > Settings > Installation Settings > Equipment > Furnace > Fan Control in Heat Mode > HVAC. In your case that means never using the furnace. After trying just about everything, I had the HVAC guy come out and install a honeywill programmable thermostat. Set the HVAC to Auto. Back … Out of the box, the Ecobee doesn't work that way. Dec 12, 2020 | Smart Thermostats, Troubleshooting. If your Ecobee smart thermostat isn’t turning on your heater, your heat set point, or desired temperature, may be the same or lower than the current temperature in your home. Specific thermostat settings may be preventing the heat from turning on. There are work-arounds (cap the aux heat wire instead) but are not as clean. The ecobee will not be compatible with high-voltage systems. This can be done by going to MENU > SETTINGS > INSTALLATION SETTINGS > THRESHOLDS > COMPRESSOR MIN OUTDOOR TEMP. Select Air to Air or Geothermal depending on the type of your heat pump system 3. Avoid running your heater for long periods during the winter. W2, AUX and or E (Emergency) wiring connections will normally connect to the ecobee3 W1 terminal. A subreddit for ecobee and all their smart home products. The easiest is probably the ecobee. The ecobee thermostat supports the following key concepts. Therefore, if it’s below 40 outside and the auxiliary heat isn’t working, then your heat pump will just blow lukewarm or cool air. If you have a heat pump installed: 1. They were very comfortable getting it installed and running. Finally, you can simply say, “Alexa, tell ecobee I’m cold”, and ecobee will automatically raise the temperature in your home. For the past two years, whenever the outdoor temp has dropped below 40 degrees or so, the aux heat is supposed to kick in. The big issue is that Ecobee's installation directions say to not hook up the emergency heat wire if you already have aux heat. ecobee3 manages auxiliary heating through the W1 & W2 (if there is more than 1-stage of aux heat… Which is extremely easy to do with an Ecobee thermostat. I have been searching the internet and found a few different ... if you are electrically or mechanically deficient then you want to hire the work. Then, use the slider on the main display screen to increase or decrease the desired temperature. Unlock energy savings on heating and cooling and enhanced comfort with eco+, a free software upgrade for ecobee thermostats. An overheated furnace can cause a fire, so furnaces have an automatic shut-down trigger for safety. Troubleshooting accessory installations; I’m getting heat when calling for air conditioning. Recently, I installed an Ecobee 3 thermostat and now appear to have no aux or - Answered by a verified HVAC Technician We use cookies to give you the best possible experience on our website. The A/C ran fine all summer, but now the heat is not working properly. Help! This should all be happening automatically between the heat pump and furnace. It cannot be done using the Ecobee app or website. Installation I reinstalled the old thermostat and it is working as expected (heat + fan). Even in the depths of winter, my second floor never got over 63 degrees. Auxiliary Heat RunTime: Your auxiliary heat source is running too often. Even when the furnace has power, some users have found that switching the breaker solves their problem because it resets the furnace. Heat Pumps and Electric Home Heating - Help with auxiliary heat on heat pump - I am looking for guidance on auxiliary heat with heat pump. Why does this happen? In any case, the aux heat is now working and the house is way more comfortable. Does Chamberlain MyQ Work With Alexa? Smarthomestarter.com is a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to Amazon.com. Need help connecting my ecobee thermostat to my goodman heat pump. Ever. It was very cold last night, and the Ecobee just ran the heat pump all night long even though it … 2. Does the Nest Thermostat Work without Internet? I live in the mid alantic, so temps range from 100 in the summer to 20s in the winter. The fan may stay on to help cool down the furnace, but it will not send heat throughout your house until it has cooled down to a safe temperature. Which is extremely easy to do with an Ecobee thermostat. eco+ makes saving energy automatic. This appears to have done nothing as I am still without aux heating after running the test cycle on the thermostat. And it requires extra wiring that has to be set-up by a professional. It's currently wired up at the thermostat the way the RiteTemp instructions say (the C wire is present and hooked up), except that the W wire from the air handler is connected to the W2 terminal on the thermostat, and the Y wire is interrupted by a float switch for the drip pan. Ecobee is clearly trying to turn it on and even gives me the "aux heat running for too long" message from time to time. Look for the orange flame icon on the … Everything else in the house is gas fired heat. Adjusting these heat settings can only be done on the Ecobee thermostat interface. Smarthomestarter.com is a participant in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to Amazon.com. Contractor's Assistant: ... Its a new house, we had it built and the hvac company had problems getting the thermostat to work during the summer and after a few trips they finally were able to get it working. Press Menu on the main screen. When I have the heat on, the Ecobee indicates that the "running equipment" is the fan AND heat (even though the heat is not … If after reviewing the compatibility and installation information, you learn that an ecobee thermostat will not work for you, please consider the other smart thermostats available at our store. Other solutions to try are resetting the furnace power at the breaker box and cleaning your furnace. The ecobee doesn't even know the defrost cycle is happening and it certainly doesn't tell the aux to kick on. Try switching the breaker for the furnace power to see if that restores power. Turn it off, wait at least one minute, then turn it back on again. How can I troubleshoot? Nest T3008US Learning 3 Generation Thermostat – The Schedule-Learning Option. Not compatible with multi-stage heating and cooling, heat pump with auxiliary heat or electric baseboard heating. I have a heat pump system with aux heat. Clean and replace the air filter regularly. So it relies on an auxiliary (AUX) heat coil (like the ones you see in a toaster) or a furnace to heat your home. Since no one had made changes in the settings, I called out a repairman who found that the heat pump was not the problem, checked the settings on the Ecobee, and found that it was not allowing a dual heat source--the way it has been programmed for 5 … For now I have had success changing the system to "Off" and then back on to "Heat." I would like that as well. Therefore, if it’s below 40 outside and the auxiliary heat isn’t working, then your heat pump will just blow lukewarm or cool air. There are a few things you can do to prevent your furnace from overheating: When your Ecobee thermostat isn’t turning on the heat, the solution may be to change your heat set point, the heat threshold settings, or the fan control. If the temperature inside the furnace reaches an unsafe level, the furnace may turn off. When ecobee switches over to Aux Heat, my Wink app sends me a notification (it's the only reason I still have the Wink app on my phone, tablet, etc). The ecobee will work with about 95% of HVAC systems. Ever. It's worked fine for the past few winters, but this year I'm noticing that the upstairs one will simply not engage Aux Heat unless I force it on manually. There are two important points to note here: 1. There are four possible reasons why an Ecobee thermostat isn’t turning on the heat when it’s supposed to: Not sure if the heat is on? My ecobee is making a "clicking" noise and will not turn on! This may seem obvious, but the first thing you should do if Ecobee isn’t turning on the heat is to check the heat set point. We know you have questions, so below we’ll go into more detail about: If after reviewing the compatibility and installation information, you learn that an ecobee thermostat will not work for you, please consider the other smart thermostats available at our store. Press J to jump to the feed. Cool Not Responding: The system has failed to cool the home. Specific thermostat settings may be preventing the heat from turning on. To the ecobee, the heat is just still running. For example, you can change the minimum difference between the current temperature and the set point required to turn on the heater. It’s working! This site is owned and operated by Time Off Club, LLC. The system has failed to heat the home. Auxiliary Heat Run Time: Auxiliary heat source is running too often. Apparently, this thermostat is only configured to have aux heating go through connection W1 and cannot have something connected to only W2. But the aux heat NEVER came on. Once the thermostat has booted up, open the Quick Change menu (cog icon) and check the Wi-Fi connection icon. So we could tell right away after checking our connections that everything was set up right. Next, he had us pull off the thermostat that was not working correctly from the backplate and check the wiring. That's why, recently, I awoke feeling like I was sleeping in a sauna. Now that you know the potential causes of Ecobee not turning on the heat, you will want to know how to troubleshoot this problem. Designed by Elegant Themes | Powered by WordPress, How to Transfer your Ecobee to a New Owner. Not sure if the heat is on? Allow your Ecobee to boot up as normal. Select Aux Heat Max Outdoor Temperature; select between 30 and 45 degrees; select Save. Out of the box, the Ecobee doesn't work that way. First, make sure your thermostat is set to Heat or Auto mode. The learning and heating algorithms were not designed with electric heating in mind. Wiring that is at best, complicated, and at worst, dangerous. The HVAC unit in question is a heatpump with a 10k aux heat coil. Heat Not Responding: The system has failed to heat the home. Auxiliary Outdoor Temperature: Your auxiliary heat source is running at higher than expected outdoor temperatures. You can also tell the auxiliary heat to stop working when the temperature outside your home reaches a certain degree. AUX heat refers to your heat pump’s “backup” electric resistance heating. The other issue with not having the option for emergency heat is that you lose control. Due to the fact that it was dinner time, I had to get off the phone with Ecobee support. There are four possible reasons why an Ecobee thermostat isn’t turning on the heat when it’s supposed to: The heat point on the thermostat is set lower than the temperature in the house. However, what if your Ecobee doesn’t turn on the heat? Press question mark to learn the rest of the keyboard shortcuts. Have three ecobees installed in the house for multi zone HVAC, all of which were installed by the HVAC installer company. The furnace is not receiving power. 4) Auxiliary heat is malfunctioning Below 40 degrees, your heat pump struggles to heat your home. I'd like to pull the Honeywell and put the ecobee back ... any ideas on what could possibly have been going wrong? Some users have reported that switching their fan control from the thermostat to the furnace has worked for them when their heat wouldn’t turn on. 45 30 Select the heat pump menu. The heat point on the thermostat is set lower than the temperature in the house. Your Ecobee thermostat calls heat from your furnace, so if the furnace doesn’t have power, there will be no heat. It should be higher at least 1 degree higher than the current temperature in the house. How can I troubleshoot? Look for the orange flame icon on the thermostat display. Page 67: Auxiliary Heat W2 Y1 compressor and auxiliary Heat Pump Air Handler heat, if applicable NOTE Do not connect any jumper wires between Rc and Rh. The R wire needs to go into the Rc terminal on your ecobee. Google … Ecobee is clearly trying to turn it on and even gives me the "aux heat running for too long" message from time to time. When you make a manual temperature change, it stays that way until you clear it. Here are the directions to adjust the heat threshold settings: Depending on the temperature inside and outside your home, changing the heat threshold settings may allow your heat to turn on when it wasn’t before. So I left the white wire connected to W1 and disconnected the brown wire and taped it off. I then re-installed the Ecobee and when I turn on the heat only the fan starts up - the heat doesn't even attempt to kick on. Then select HVAC. Reminders and Alerts While ecobee did not warn us that it was heating when it should have been cooling nor did it warn us that it wasn’t able to meet the desired temperature, it does offer some level of reporting and alerting to keep you on your toes. If the flame icon is white, the thermostat is not calling for heat. Need help connecting my ecobee thermostat to my goodman heat pump. Sometimes there is a genuine problem, but more often than not, there is nothing wrong. When I have the heat on, the Ecobee indicates that the "running equipment" is the fan AND heat (even though the heat is not … The HVAC is a heat pump, with the air handler in the attic. Cool Not Responding: The system has failed to cool the home. HVAC equipment manufacturers and the Air Conditioning Contractors of America (ACCA) do not recommend turning off the compressor at all. This is set at a default 35F (1.7C), so the heatpump will not be used when the weather outside is below 35 degrees Fahrenheit and only aux heat will be used in … For example, lowering the heat differential temperature will cause your heater to turn on sooner. ecobee does this automatically. The target temperature is either determined by the currently active climate or it may be overridden by a hold. It supports up to 2 stages for heating and 2 stages for cooling as well as up to 2 stages of auxiliary heat (so it actually supports a total of four stages for heating). If your furnace still isn’t turning on, you may need to hire an electrician to service it. This diagram illustrates the wiring connections for a heat-pump system with auxiliary heating. If it isn’t connected yet, try closing the menu, waiting a few more minutes, and then opening again. *This must be at least 5 degrees higher than your selection in Part 1, Step 6. My furnace won’t turn on! Go to System. It looked as though the heat pump had gone out since it was only running on auxiliary heat source, and there was NO warning from Ecobee. To Set Thermostat to Auto Mode. Aux Heat Runtime Alert- Sets the amount of time that the Auxiliary heat source, if installed, can run continuously before an alert is generated. Was a massive remodel, so just about everything is new. If this isn’t the first time you have had an issue with receiving power from your furnace, you may want to use the Power Extender Kit that came with your Ecobee thermostat. Contractor's Assistant: ... Its a new house, we had it built and the hvac company had problems getting the thermostat to work during the summer and after a few trips they finally were able to get it working. It's homekit compliant, which is great, but it's not the ecobee I bought. As we head into winter, you will likely be using your Ecobee smart thermostat for heat more often. 1 Like. Keep in mind that changing these settings may also increase your utility bill or put extra stress on your HVAC system. I then re-installed the Ecobee and when I turn on the heat only the fan starts up - the heat doesn't even attempt to kick on. Clean the furnace’s blower fan and evaporator coil every year. When the thermostat is not in auto mode, there is a single target temperature. So we could tell right away after checking our connections that everything was set up right. 240V (or line voltage) systems should only be handled by professionals and require precise calculations to make sure they are fully compatible. Changing the heat set point can be done on the thermostat interface or in the app. But the aux heat NEVER came on. This site is owned and operated by Time Off Club, LLC. So it relies on an auxiliary (AUX) heat coil (like the ones you see in a toaster) or a furnace to heat your home. We’ve always been using an old simple thermostat for use with the house’s stove which uses a millivolt connection. That's why, … Unfortunately, in extremely cold weather, even a properly working heat pump does not reach temperature set on thermostat. See More + The Emerson P210C thermostat is a 5-1-1 day programmable thermostat that allows you set convenient weekday / Saturday and Sunday schedules.This thermostat features backlit display and precise temperature control of plus/minus 1. Pre-heat or cool your home from the app if arriving earlier than expected. I created this video with the YouTube Video Editor (http://www.youtube.com/editor) Check to make sure the vents are clear; there shouldn’t be anything directly in front of them. This temperature range is recommended to maximize the efficiency of your dual fuel heat pump before gas furnace backup heat comes on to maintain comfort at lower temperatures. The current thermostat is a RiteTemp 6025. I have two heat pumps each with an Ecobee3. This heat setting should only kick on when the heat pump can’t produce enough heat to warm your home or if your heat pump goes into defrost mode.

Tracked Mini Crane, Im Cool Gif Hercules, The Shoe Box 25th Anniversary Edition Francine Rivers, Home Protection Scheme, Jessica Morris Net Worth, Old Gregg Quotes Make An Assessment,